Switch Gld11-32A Positions Rotary Cam Universal Changeover Switch

Product Details
Customization: Available
Rotary Number: Three Buttons
Usage: Electrical Appliance, Machinery
Manufacturer/Factory & Trading Company
Gold Member Since 2016

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
115
Year of Establishment
2016-02-02
Find Similar Products

Basic Info.

Model NO.
Gld11-32A
Structure
Self-Locking
Operation
Open Type
Certification
ISO, CE
Condition
New
Performance
Well
Universal Changeover
Switch
Transport Package
Carton
Specification
CCC, CE
Trademark
PAGELE
Origin
Wenzhou, Zhejiang
HS Code
8536500000
Production Capacity
60, 000 PCS/Per Month

Product Description

Product Description


LW28 series changeover switch


Scope

LW28 Series Universal changeover switch mainly used for AC 50Hz, rated voltage up
To 380V and below, DC voltage up to 220V, rated current to 160A electrical circuit for
Manually infrequent making or breaking the circuit for the purposes of control and
Conversion, can also controlling three-phase asynchronous motors and circuit
Directly as the purposes of master control and measurement. The products widely
Used, instead of the various national switch, can be used as the circuit control switch,
Measuring equipment switches, motor control switches and the master control
Switch, and welding machine switch and so on.
Compliance with standards: The changeover switch use to the main circuit switching
And direct control comply with GB14048.3-2001 contactor switch


Normal Working Conditions

1. The ambient air temperature does not exceed +40º C, the average temperature
Within 24 hours and not more than +35º C.
2. The ambient air temperature is not lower than -5º C.
3. Installation site altitude does not exceed 2000m.
4. The relative humidity of the air no more than 50% when the maximum
Temperature is +40º C and at a lower temperature allows a higher relative
Humidity, such as when temperature is 20º C the relative humidity reach 90%.
To condensation occasionally due to temperature changes should take special
Measures.
1.Specifications                            
Type Ith  A Ui  V Ue V    AC-21A   AC-22A AC-23A               AC-2                    AC-3                    AC-4      AC-15          DC-13 
Ie Ie Ie P Ie P Ie P Ie P Ie
A A A kw A kw A kw A kw A
  20 660 440 20 20 15 7.5 15 7.5 11 5.5 3.5 1.5 4
LW28-20 240                     5
  120                      
  25 440 25 25 22 11 22 11 15 7.5 6.5 3 5
LW28-25 240                     8
  120                      
  32 440 32   30 15 30 15 22 11 11 5.5 6
LW28-32 240                     14
  120                      
LW28-63 63 440 63   57 30 57 30 36 18.5 15 7.5  
  120                      
LW28-125 125 125 125 125 100 45 100 45 50 22 18 12  
LW28-160 160 160 160 160 115 57 115 57 65 33 25 15  
                             

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier